Spring-clamp installation

The Spring-clamp range is designed to ground and retain all types of braided cables in particular SY and CY cables.

The Spring-clamp cable gland has a waterproof plastic outer and  the core of the fitting is Electroless Nickel plated aerospace grade aluminium.

The grounding and anchorage is via a twin torsion spring.

The Automatic Grounding System (AGS) is achieved via hardened teeth on the conductive body interface.


sc 2
Tighten and loosen quarter turn several times until the paint is removed, note the paint chippings.


sc 2
Prepare cable with about 15~20mm of flared braid.
Press exposed braid back over grounding profile and open the spring arrangement using grips or pliers.


 

sc 3
Finished termination

sc 4
A compact waterproof plastic outer gland.

sc 5
The milliohm test meter reads 7 milliohm DC resistance continuity to the earth bar from the braid.

Back to Top